Six Amp Hazardous Area Series Surge Protectors

Product Line : IS-SSP6A

Six Amp Hazardous Area Series Surge Protectors

For DC and AC power up to 6A, no follow current Ex ia

Novaris IS-SSP6A series surge protectors complement the IS-SL range for applications with load currents up to 6A. These may include power supplies, digital outputs and other low voltage systems. This product is free from AC follow on current under all conditions and may safely be used to protect battery backed power supplies. These products are certified Ex ia for use in hazardous areas.

  • 6A load current
  • Visual health indicator
  • Replaceable cartridge
  • 7mm width
  • No follow on current
  • Zero earth leakage
SpecificationsIS-SSP6A-14IS-SSP6A-26IS-SSP6A-38IS-SSP6A-65
Maximum continuous voltage (DC)U꜀14V26V38V65V
Maximum continuous voltage (AC)U꜀11V20V30V50V
Maximum discharge current (8/20μs)Iₘₐₓ5kA per line (10 kA common mode)
Impulse durabilityC2 8/20μs 5kA
Maximum load current

IL

6A6A6A6A
L-L Voltage protection level @ 1 kV/μsUₚ4565110135
L-PE Voltage protection level @ 1 kV/μsUₚ380V380V380V380V
Line resistance0.02 Ω0.02 Ω0.02 Ω0.02 Ω
Earth Isolation Versions-EC90
Dimensions📐W 7mm X H 102mm X D 68mm
Weight📦35g
Product DatasheetPDFIS-SSP6A-14IS-SSP6A-26IS-SSP6A-38IS-SSP6A-65