Two Pair 500mA Signal Line Protectors

Product Line : SL4

Two Pair 500mA Signal Line Protectors

For two twisted pairs

Novaris SL4 plug-in signal line protectors provide surge protection for most dual twisted pair signalling schemes. They are ideal for the protection of PLCs, fire and security systems, telecommunications, telemetry systems, railway signalling, SCADA and other industrial monitoring and control equipment with a load current up to 500mA.

  • 20 kA surge rating
  • Visual health indicator
  • Replaceable cartridge
  • For earth isolation use SL1-G90
  • Multistage protection
  • Failsafe design
SpecificationsSL4-7v5SL4-18SL4-36SL4-68SL4-RTD
Maximum continuous voltage (DC)U꜀7V16V34V65V7V
Maximum continuous voltage (AC)U꜀5V11V24V46V5V
Maximum discharge current (8/20μs)Iₘₐₓ10kA per line (20kA common mode)10kA per line (20kA common mode)10kA per line (20kA common mode)10kA per line (20kA common mode)10kA per line (20kA common mode)
Maximum impulse current (10/350μs)Iᵢₘₚ2.5kA per line (5kA common mode)2.5kA per line (5kA common mode)2.5kA per line (5kA common mode)2.5kA per line (5kA common mode)2.5kA per line (5kA common mode)
Impulse durabilityC2 8/20μs 10kA – D1 10/350μs 5kAC2 8/20μs 10kA – D1 10/350μs 5kAC2 8/20μs 10 kA – D1 10/350μs 5kAC2 8/20μs 10kA – D1 10/350μs 5kAC2 8/20μs 10kA – D1 10/350μs 5kA
Maximum load current

IL

500mA500mA500mA500mA500mA
L-L Voltage protection level @ 1 kV/μsUₚ15V30V40V80V15V
L-PE Voltage protection level @ 1 kV/μsUₚ350V350V350V350V350V
Line resistance3.9 Ω3.9 Ω3.9 Ω3.9 Ω3.9 Ω
Dimensions📐W 12mm X H 110mm X D 71mm
Weight📦75g
Product DatasheetPDFSL4-7v5SL4-18SL4-36SL4-68SL4-RTD