One Pair Threaded Signal Protectors - Hazardous Area

Product Line : IS-SLT1

One Pair Threaded Signal Protectors - Hazardous Area

For one pair threaded body Ex ia Exd

Novaris IS-SLT1 one pair threaded instrument protectors provide surge protection for twisted pair signalling schemes. They are designed to be installed directly at field equipment, providing protection against induced surges and transients.

  • IEC Ex ia and Ex d approved
  • IP 67 rated
  • M20, M25 and 1/2” NPT thread options
  • 10 kA protection
  • 316 stainless steel
    SpecificationsIS-SLT1-7v5IS-SLT1-18IS-SLT1-36
    Maximum continuous voltage (DC)U꜀7V16V34V
    Maximum continuous voltage (AC)U꜀5V11V24V
    Maximum discharge current (8/20μs)Iₘₐₓ5kA per line (10kA common mode)
    Maximum impulse current (10/350μs)Iᵢₘₚ1.25kA per line (2.5kA common mode)
    Impulse durabilityC2 8/20μs 2kA – D1 10/350μs 0.5kA
    L-L Voltage protection level @ 1 kV/μsUₚ40V50V75V
    L-PE Voltage protection level @ 1 kV/μsUₚ350V350V350V
    DimensionsW 25mm X H 29mm X D 53mm
    Weight165g
    Product DatasheetPDFIS-SLT1-7v5IS-SLT1-18IS-SLT1-36
    Installation GuidePDFIS-SLT1-7v5IS-SLT1-18IS-SLT1-36