Combined Signal Protectors

Product Line : SLC

Combined Signal Protectors

For combination power and signal

Novaris SLC combined signal protectors provide surge protection for common combined twisted pair signalling systems. The SLC-24-36 provides protection for 24V power and 24V signals. The SLC-12-485 and SLC-24-485 provide protection for 12V power/RS485 signals and 24V power/RS485 signals respectively.

  • 10 kA surge rating
  • Visual health indicator
  • Replaceable cartridge
  • For earth isolation use SL1-G90
  • Multistage protection
  • Failsafe design
SpecificationsSLC-24-36SLC-12-485SLC-24-485
Maximum continuous voltage (DC)U꜀36V (power)
34V (signal)
18V (power)
8V (signal)
36V (power)
8V (signal)
Maximum continuous voltage (AC)U꜀25V (power)
24V (signal)
12V (power)
6V (signal)
25V (power)
6V (signal)
Maximum discharge current (8/20μs)Iₘₐₓ7.5kA(power)
10kA (signal)
5kA (power)
10kA (signal)
5kA (power)
10kA (signal)
Maximum impulse current (10/350μs)Iᵢₘₚ5kA (signal)5kA (signal)5kA (signal)
Impulse durabilityC2 8/20μs 10kA – D1 10/350μs 5kAC2 8/20μs 10kA – D1 10/350μs 5kAC2 8/20μs 10kA – D1 10/350μs 5kA
Maximum load current

IL

10A (power)
500mA (signal)
2A (power)
500mA (signal)
2A (power)
500mA (signal)
L-L Voltage protection level @ 1 kV/μsUₚ65V (power)
40V (signal)
45V (power)
15V (signal)
65V (power)
15V (signal)
L-PE Voltage protection level @ 1 kV/μsUₚ350V (power)
350V (signal)
350V (power)
350V (signal)
350V (power)
350V (signal)
Line resistance3.9Ω (signal)3.9Ω (signal)3.9Ω (signal)
Dimensions📐W 12mm X H 110mm X D 71mmW 12mm X H 110mm X D 71mmW 12mm X H 110mm X D 71mm
Weight📦65g65g65g
Product DatasheetPDFSLC-24-36SLC-12-485SLC-24-485
Installation GuidePDFSLC-24-36SLC-12-485SLC-24-485